Cooler Master RC-1010 Manual de Instalação

Consulte online ou descarregue Manual de Instalação para Aparelhos de ar condicionado "split system" Cooler Master RC-1010. Cooler Master RC-1010 Installation manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - INSTRUCTION

SPLIT TYPEROOM AIR CONDITIONERWALL MOUNTEDtypeModels Indoor unit Outdoor unitINVERTERSERVICEINSTRUCTIONR410AASU 9RLFASU12RLFASU15RLSAOU 9RLFWAOU12RLFW

Página 2 - CONTENTS

7. LOUVER CONTROL1. VERTICAL LOUVER CONTROL2. SWING OPERATIONEach time the button is pressed, the air direction range will change as follow:(Function

Página 3

8. COMPRESSOR CONTROL1. OPEARTION FREQUENCY RANGEThe operation frequency of the compressor is different based on the operation mode asshown in the tab

Página 4 - 1-1 COOLING CAPACITY CONTROL

9. TIMER OPEARTION CONTROL1. OPEARTION FREQUENCY RANGEThe table11 shows the available timer setting based on the product model.ON TIMER / OFF TIMER PR

Página 5 - 3-1 INDOOR UNIT CONTROL

3. SLEEP TIMERIf the sleep is set, the room temperature is monitored and the operation is stopped automatically.If the operation mode or the set tempe

Página 6 - 4. AUTO CHANGEOVER OPERATION

10. ELECTRONIC EXPANSION VALVE CONTROLThe most proper opening of the electronic expansion valve is calculated and controlled under thepresent operatin

Página 7 - 5. INDOOR FAN CONTROL

15. MANUAL AUTO OPERATION (Indoor unit body operation)If MANUAL AUTO Button is set, the operation is controlled as shown in Table13.If the remote cont

Página 8 - 5. HEATING OPERATION

20. DEFROST OPERATION CONTROL01-131. CONDITION OF STARTING THE DEFROST OPERATIONThe defrost operation starts as shown in the following Table 16.2. CON

Página 9 - 6. OUTDOOR FAN CONTROL

01-14Outdoor fan : OFFCompressor speed:0rpsEEV : 480pulse4-way valve : OFFCompressor speed : 90rps (09/ 12)70rps (15)3. Defrost Flow ChartThe defrosti

Página 10 - 7. LOUVER CONTROL

21. OFF DEFROST OPEARTION CONTROL1. OFF DEFROST OPERATION CONDITIONWhen operation stops in the [Heating operation] mode, if frost is adhered to the ou

Página 11 - 8. COMPRESSOR CONTROL

22. VARIOUS PROTECTIONS1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROLThe discharge gas thermosensor (discharge thermistor : Outdoor side) wi

Página 12 - 9. TIMER OPEARTION CONTROL

CONTENTS1. DESCRIPTION OF EACH CONTROL OPERATION1. COOLING OPERATION...

Página 13

3. ANTIFREEZING CONTROL (Cooling and Dry mode)The compressor frequency is decrease on cooling & dry mode when the indoor heat exchangertemperature

Página 14 - 14. AUTO RESTART

2 . TROUBLE SHOOTINGR410AWALL MOUNTED typeINVERTER

Página 15 - ECONOMY OPERATION

2. TROUBLESHOOTING02-012-1 ERROR DISPLAYWhen "Er" in Temperature Display is displayed, inspection of the air conditioning system is necessar

Página 16 - 20. DEFROST OPERATION CONTROL

02-022. ERROR CODE HISTORY DISPLAYUp to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.1. Stop the a

Página 17 - 3. Defrost Flow Chart

02-031. ERROR DISPLAY2-1-3 INDOOR UNIT DISPLAYError contentsOperation lamp(Green)TroubleshootingTimer lamp(Orange)4 times flash1 times flash1 times fl

Página 18 - Over 60.8°F (16°C) or

02-042-2 TROUBLE SHOOTING WITH ERROR CODETrouble shooting 1-1OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:OKIndic

Página 19 - 22. VARIOUS PROTECTIONS

02-05Trouble shooting 1-2INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:OKIndicate or Display:YESYESNOOKSerial commu

Página 20

Trouble shooting 2INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 2 : Check Remote Control and Controller

Página 21 - WALL MOUNTED type

Detective Actuators:Detective details:Forecast of Cause:Check Point 3 : Replace Controller PCBCheck Point 2 :Check Indoor unit electric componentsYESY

Página 22 - 2. TROUBLESHOOTING

02-08Trouble shooting 4INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKManual aut

Página 23 - 2-1-2 OUTDOOR UNIT DISPLAY

1 . DESCRIPTION OF EACHCONTROL OPERATIONR410AWALL MOUNTED typeINVERTER

Página 24 - 2-1-3 INDOOR UNIT DISPLAY

Trouble shooting 5INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :Chec

Página 25

Trouble shooting 6INDOOR UNITINDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :62.9

Página 26

Trouble shooting 7INDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 1 : Check rotation of FanCheck Point 2

Página 27

Detective Actuators:Detective details:Forecast of Cause:Check Point 2 : Replace Main PCBYESYESNOTrouble shooting 8OUTDOOR UNIT Error Method:Indicate o

Página 28

Trouble shooting 9INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKOKOKPFC circui

Página 29 - INDOOR UNIT

Trouble shooting 10OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 3 : Check Outdoor FanOKOKIndicate or

Página 30

Trouble shooting 11INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :Ch

Página 31 - Check Point 2 :

Trouble shooting 12OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :6.09.612.416.121.027.8Resistance

Página 32

Trouble shooting 13OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 :26.935.246.662.384.2115.2Resistan

Página 33

Trouble shooting 14OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 4 : Replace Main PCBYESNOOKIndicate

Página 34

( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )1. COOLING OPERATION1-1 COOLING CAPACITY CONTROLA sensor (room temperature thermist

Página 35

Trouble shooting 15OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :OKOKIndicate or Display:Check Point 2: Replace M

Página 36

Trouble shooting 16OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause :Check Point 2 : Check connection of around the C

Página 37 - Check Point 3 :

Trouble shooting 17OUTDOOR UNIT Error Method:Detective Actuators:Detective details:Forecast of Cause:Check Point 3 : Check Outdoor unit fan motorOKOKI

Página 38

Trouble shooting 18INDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :OKOKOKOK4-way valve errorIndo

Página 39

Trouble shooting 19INDOOR UNITOUTDOOR UNIT Error Method:Indicate or Display:Detective Actuators:Detective details:Forecast of Cause :Discharge tempera

Página 40

Trouble shooting 20Forecast of Cause:OKOKIndoor Unit - No Power1. Power Supply failure 2. External cause3. Electrical Components defectiveCheck Point

Página 41

Trouble shooting 21Forecast of Cause:Check Point 3 : Check Electrical ComponentsOKOKOKOKYESYESOKNOCheck Point 1 : Check Installation ConditionOutdoor

Página 42

Trouble shooting 22Forecast of Cause:Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)Check Point 1 : Check indoor an

Página 43

AttentionTrouble shooting 23Forecast of Cause:Check Point 2 : Check Outdoor Unit OperationCheck Point 1 : Check Indoor UnitCheck Point 3 : Check Site

Página 44

Trouble shooting 24Forecast of Cause :Trouble shooting 25Forecast of Cause:OKOKOKOKOKOKOKOKOKOKMPa MPaAbnormal Noise1. Abnormal installation (Indoor/

Página 45 - Indoor Unit - No Power

2. HEATING OPERATION2-1 HEATING CAPACITY CONTROLA sensor (room temperature thermistor) built in the indoor unit body will usually perceivedifference o

Página 46 - Outdoor Unit - No Power

SERVICE PARTS INFORMATION 1MPa MPaCompressorDiagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )Does not s

Página 47

SERVICE PARTS INFORMATION 2Check Point 1 : Check ConnectionCheck Point 2 : Check Winding ResistanceCheck Point 3 : Replace Main PCBCSRInverter Compres

Página 48 - No Cooling / No Heating

SERVICE PARTS INFORMATION 3Check Point 2 : Check Coil of EEVYellow - RedOrange - RedBlue - RedWhite - RedRead wire464Resistance valueCheck Point 1 : C

Página 49 - Water Leaking

SERVICE PARTS INFORMATION 5Check Point 1 : Check rotation of FanOutdoor unit fan motorRotate the fan by hand when operation is off.(Check if fan is ca

Página 50 - 2-4 SERVICE PARTS INFORMATION

3 . APPENDING DATAR410AWALL MOUNTED typeINVERTER

Página 51 - Inverter Compressor

03-013-1. FUNCTION SETTINGFollow the instructions in the Local Setup Procedure, which is supplied with the remote control,in accordance with the insta

Página 52

03-02( Factory setting)Setting DescriptionFunction Number Setting ValueYesNo400001( Factory setting)Setting DescriptionFunction Number Setting ValueNo

Página 53 - Indoor unit fan motor

MIN.HEATMIN.HEATMIN.HEAT03-03Settings will not be changed if invalid numbers or setting values are selected.After the power is turned on, perform the

Página 54

03-04(1) Press the MODE button for more then 5 seconds.(3) Press the MODE button. (Return to normal display)Custom code setting for remote controller(

Página 55 - 3-1-1 INDOOR UNIT

-10.0 58.2 0.73-30.0 1131.9 0.21-5.0 44.0 0.93 -25.0 804.5 0.290.0 33.6 1.15 -20.0 579.6 0.405.0 25.9 1.39 -15.0 422.9 0.5310.0 20.2 1.66 -10.0 312.3

Página 56

4. AUTO CHANGEOVER OPERATION01-03Operation flow chartSTARTRoom temp.Room temp.>Ts+4°F(2°C)?COOLING OPERATIONHEATING OPERATIONYESYESNONONONOYESYESTS

Página 57 - Setting Value

1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,JapanSep. 2010 Printed in Japan

Página 58

5. INDOOR FAN CONTROLThe airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,while the indoor fan only runs.When Fan mode is set at

Página 59 - 3-2-2 OUTDOOR UNIT

The maximum value of the indoor fan speed is set as shown in Figure5, based on the detectedtemperature by the indoor heat exchanger sensor on heating

Página 60 - Sep. 2010 Printed in Japan

6. OUTDOOR FAN CONTROL( Table7 : Outdoor fan speed )*The outdoor fan speed mentioned above depends on the compressor frequency.(When the compressor fr

Comentários a estes Manuais

Sem comentários